Set Flow Sensor Model
Flow Sensor Data Table
Step 1 – Place the Function dial to the FLOW
SENSING position. Enable
ow sensing if its disabled.
Step 2 – While in the K Value/Sensor Size
screen, select the ow sensor size
code by pressing the button.
Use the Flow Sensor table below to
nd your specic size code.
Example: If using Sensor Model
TFS-075, press the button until
the S value in the display equals 75
(S=75).
Set Flow Unit
Step 1 – Place the Function dial to the FLOW SENSING position. Enable ow sensing if its disabled.
Step 2 – Press the button to change the ow unit. Press the button repeatedly until the desired ow unit is
displayed (GPM = Gallons per Minute, CFM = Cubic Feet per Minute, CMH = Cubic Meter per Hour,
LPM = Liter per Minute or PPS = Pulses per Second).
If the sensor you choose is not represented on the chart, use “Unknown Flow Sensor” size code “00”. The ow
unit for “Unknown Flow Sensor” can only be set to PPS.
Read/Learn Station Flow Value
Step 1 – Place the Function dial to the FLOW SENSING position. Enable ow sensing if its disabled.
Step 2 – Verify that all ow parameters are set, then press the button to read/learn each of the station’s actual
ow. It will read/learn the station’s ow value until the ow delay time expires. The default ow delay is one
minute. During “Learn Flow” each station will be displayed with the ow that the sensor is measuring.
To learn the ow value of a specic station, enter the two digit station number and press the button.
To learn the ow value of a group of stations, enter the two digit station number of the 1st station, the two digit
station number of the last station and press the button. The MC-E will sequentially read the ow value for
each station in the group.
Step 6 – To review each station ow parameters, press the button. MC-E will sequentially display each of the
station’s ow parameters.
Flow Sensor Model K Value Offset GPM L/Sec
Size
Code
Pipe
Size
Unkown Flow Sensor 00 Unkown 1 0 PPS PPS
TFS-050 50 1/2 0.07800 0.9 1.2 – 12 0.1 – 0.8
TFS-075 75 3/4 0.15630 0.9 2.7 – 28 0.2 – 1.8
TFS-100 100 1’’ 0.26112 1.2 5.0 – 50 0.3 – 3.2
TFS-150 or 228PV15xx-xxxx 150 1.5 1.69900 -0.3160 5 – 100 0.3 – 6.3
TFS-200 or 228PV20xx-xxxx 200 2.0 2.84290 0.14350 10 – 200 0.6 – 12.6
TFS-300 or 228PV30xx-xxxx 300 3.0 8.30900 0.22700 20 – 300 1.3 – 18.9
TFS-400 or 228PV40xx-xxxx 400 4.0 13.74283 0.23707 40 – 500 2.5 – 31.5
250BR0700x-xxxx 7 3/4 0.43680 0.56800
250BR1000x-xxxx 10 1’’ 0.39740 0.26180
0.25 Liters Per Pulse 11 0.25 L/P 1 0
0.50 Liters Per Pulse 12 0.50 L/P 1 0
1 Liter Per Pulse 13 1 L/P 1 0
2.5 Liters Per Pulse 14 2.5 L / P 1 0
5 Liters Per Pulse 15 5 L/P 1 0
10 Liters Per Pulse 16 10 L/P 1 0
25 Liters Per Pulse 17 25 L/P 1 0
50 Liters Per Pulse 18 50 L/P 1 0
100 Liters Per Pulse 19 100 L/P 1 0
250 Liters Per Pulse 20 250 L/P 1 0
500 Liters Per Pulse 21 500 L/P 1 0
1000 Liters Per Pulse 22 1000 L/P 1 0